What this is
What is a fire door inspection?
What is a fire door inspection?
A fire door inspection is a periodic check that a fire-rated door assembly still performs its function: it closes fully from any open position, latches, is not propped or wedged open, and its seals, glazing and hardware remain undamaged. It verifies the assembly as installed, not the rating decision behind it.
Who carries out a fire door inspection?
Facilities, on the site's stated cycle. This is a functional and condition check rather than the annual technical examination NFPA 80 requires from a qualified person, and the two should not be treated as interchangeable even though both leave a record against the same door.
Why does a door being propped open matter if it gets closed straight away?
Because closing it once fixes the symptom for that inspection, not the reason it was propped. A door propped for ventilation, traffic flow or moving materials will be propped again unless the cause is addressed, and the compartment it protects is unprotected for every minute it stands open in between.
Scope
When is a fire door inspection required?
This inspection is one step in a larger programme. Using it for work that belongs to a neighbouring template, or letting a repeat propping finding close without investigation, produces records that look complete and protect nothing.
Use this template when
- The routine inspection cycle for the site is due
- A door was serviced, repaired or had its closer replaced and needs re-checking in position
- A previous inspection raised an action, and the fix needs to be verified as closed
- A door was found propped between cycles and the finding needs a formal record
- Compartmentation was set or changed by a Fire Risk Assessment and the affected doors need their first check against the new plan
Do not use it for
- Fire Extinguisher Inspection, which checks portable extinguishers, not doors.
- Fire Alarm System Check, which records detection, sounders and panel function.
- Sprinkler System Inspection, which checks sprinkler heads, valves, gauges and clearance below heads.
- Fire Risk Assessment, which is the instrument that decides which doors need to be fire-rated and where; this inspection assumes rather than re-derives that plan.
- New door installation certification, the labelling and commissioning step carried out by the assembly's installer, which this inspection assumes was already done correctly
Compliance mapping
Which NFPA 80 requirements does this satisfy?
NFPA 80 treats a fire door as an assembly whose rating depends on every component, leaf, frame, seals, glazing, hardware, remaining as tested. Inspection and functional testing are addressed as a distinct chapter from the compartmentation decision that determines which doors need to be rated at all.
| Clause | Requirement | Where it lands |
|---|---|---|
| NFPA 80 sec.5.2.1 | Functional inspection and testing performed at a defined frequency, with an annual examination by a qualified person | Doors |
| NFPA 80 sec.5.2.4 | Door assembly closes fully and latches from any open position without manual assistance | Doors |
| NFPA 80 sec.5.2.4 | Gaps, seals, glazing and hardware remain within the tolerances and condition set by the assembly's listing | Doors |
| NFPA 80 sec.5.1.4 | No unauthorised field modification, hole or penetration that would void the assembly's fire rating | Doors |
| NFPA 80 sec.5.2.4 | Door assembly not blocked, wedged or held open other than by a listed, alarm-released device | Propping investigation |
| NFPA 80 sec.5.2.4 | Hold-open devices release automatically on alarm activation | Doors |
| NFPA 80 ch.5 | Written record of each inspection kept and available to the authority having jurisdiction | Result |
What it does not cover
- Fire Extinguisher Inspection, which checks each extinguisher is present, charged, unobstructed and within service date.
- Fire Alarm System Check, which records testing of detection, sounders and panel function.
- Sprinkler System Inspection, which checks sprinkler heads, valves, gauges and clearance below heads.
- Fire Risk Assessment, which is the instrument that decided which doors need to be fire-rated and where, and which this inspection assumes rather than re-derives.
- New door installation certification, the labelling and commissioning check carried out by the assembly's installer at the point of fitting, which this inspection does not repeat.
Global
Fire Door Inspection requirements by country
Fire door duty splits between a product and rating standard, which sets what the door must be capable of, and an inspection regime, which is far less consistently mandated by frequency.
NFPA 80, adopted by reference in most state and local fire codes
Annual inspection and functional testing by a qualified person is required, with the fourteen-point checklist forming the technical basis.
A local authority having jurisdiction will typically cite the NFPA 80 clause directly when a door fails inspection, rather than a separate local rule.
Regulatory Reform (Fire Safety) Order 2005; BS 8214 guidance on timber fire door assemblies
The responsible person carries a general duty to maintain fire doors in efficient working order; BS 8214 supplies the practical inspection detail the Order does not.
There is no single UK-mandated inspection frequency, so an auditor checks against BS 8214 guidance and whatever cycle the site has committed to and can evidence.
EN 16034 and EN 1634-1 (fire door product and fire-resistance test standards)
These set what a door assembly must achieve to be rated; they do not themselves mandate an ongoing inspection regime.
Sites outside North America without a local inspection mandate frequently adopt NFPA 80's inspection chapter voluntarily, because no equivalent international inspection standard fills the gap.
How to complete it
How to complete a fire door inspection, step by step
The template checks whether the door still does what it was rated to do. It depends on the propping finding being treated as a workflow question, not just a closing action.
Closing a wedged door resolves the inspection moment, not the cause. The 'why it was propped' field is the only part of the record that lets a repeat pattern be seen and acted on rather than corrected identically every cycle.
A hole drilled for a cable or pipe run voids the rating regardless of how well the door still closes and latches. The closing test and the rating are not the same question, and a door can pass one while having already failed the other.
Intumescent and smoke seals, and any glazing, were tested as part of the assembly's listing. Damage or a missing seal is not cosmetic; it is a documented reduction in what the door was proven to do, and should be repaired to the original specification, not a generic substitute.
A clean run of quarterly results does not mean the annual NFPA 80 examination is current. Track the annual date separately, and do not let a good functional check quietly stand in for the technical one.
What auditors find
Most common fire door inspection findings
Fire door findings cluster around two failure types: the door no longer performs, or it was propped and the reason was never captured.
| Finding | Clause | What fixes it |
|---|---|---|
| Door found propped or wedged open at the time of inspection. | NFPA 80 sec.5.2.4 | Close it immediately, record the reason it was propped, and route repeat cases to a workflow or hardware change. |
| Self-closer fails to fully close or latch the door from an open position. | NFPA 80 sec.5.2.1 | Adjust or replace the closer and take the door out of reliance until it closes and latches correctly. |
| Intumescent or smoke seal damaged, missing, or substituted with an unlisted product. | NFPA 80 sec.5.2.4 | Replace with a seal matching the assembly's original listing; do not use a generic strip. |
| Unauthorised penetration through the door leaf, such as a cable or pipe run. | NFPA 80 sec.5.1.4 | Remove or properly fire-stop the penetration to the assembly's listing, and treat the door as failed until corrected. |
| Hold-open device does not release the door automatically on alarm activation. | NFPA 80 sec.5.2.4 | Test and repair the release mechanism, and take the door out of service as a held-open unit until verified. |
| Same door recorded as propped on multiple prior inspections with no cause ever logged. | NFPA 80 sec.5.2.4 | Investigate the recurring traffic, ventilation or workflow cause and consider a listed hold-open-release device rather than repeating the same corrective closure. |
Case in point
Case in point: the door that kept getting propped and no one asked why
A distribution site's quarterly fire door inspection had passed a warehouse door on every measured question for over a year: closed fully, latched, self-closer functioned, seals intact. On four separate occasions the door was also found propped open with a pallet, closed on the spot each time, and the 'why it was propped' field left blank because closing it felt like the finding had already been dealt with.
A fire started in adjacent racking on a morning when forklift traffic through that doorway was heaviest. The door was propped at the time, as it usually was during that shift pattern, and the compartment it was meant to hold stayed open long enough for smoke to spread into the next bay before anyone reached it. The investigation found the same door had been propped and closed four times in the prior year with no reason ever recorded, so nobody had connected the pattern to a genuine layout problem, a doorway on the busiest forklift route with no dedicated pass-through, that a listed hold-open-release device would have solved months earlier.
The template
The template, field by field
The form exactly as it installs. Every field, option, score and conditional rule is editable, and the links to other templates come with it.
5 sections
- Reference
- SAF-114
- Archetype
- Inspection
- Record ID
- INSP-2026-000
- Scoring
- Pass or fail per door
- Direction
- High is good
- Singleton
- No
- Basis
- NFPA 80
- Links
- Links Site
- Tags
- Fire, Inspection
- Sections
- 5
- Fields
- 40
- Follow up fields
- 6
- Repeating sections
- 1
- Links out
- 4
Header
8 fieldsInspection ID*
Auto sequence. Format INSP-2026-00000.
The record's own ID. Other templates point at this value.
Status*
Drives who this goes to next.
- Planned2 pts
- In progress2 pts
- Complete3 pts
- Deferred0 pts
- Open0 pts
- Closed3 pts
- Overdue0 pts
Date and Time*
Completed By*
Site*
Site ID*
Format SITE-000.
Links to FDN-001 Site ID
Area*
The area within the site.
Exact Location
Drop a pin for anything hard to find.
Doors
Repeats18 fieldsDoor Reference*
Location*
Fire Rating
Closes Fully From Any Position*
- Pass2 pts
- Partial1 pt
- Fail0 pts
- N/Aexcluded from denominator
Latches Correctly*
- Pass2 pts
- Partial1 pt
- Fail0 pts
- N/Aexcluded from denominator
Self Closer Functions*
- Pass2 pts
- Partial1 pt
- Fail0 pts
- N/Aexcluded from denominator
Not Propped Or Wedged Open*
The most common finding, and the one that makes the whole compartment useless.
- Pass2 pts
- Partial1 pt
- Fail0 pts
- N/Aexcluded from denominator
Hold Open Device Releases On Alarm
- Pass2 pts
- Partial1 pt
- Fail0 pts
- N/Aexcluded from denominator
Gaps Within Tolerance*
- Pass2 pts
- Partial1 pt
- Fail0 pts
- N/Aexcluded from denominator
Intumescent Seals Intact*
- Pass2 pts
- Partial1 pt
- Fail0 pts
- N/Aexcluded from denominator
Smoke Seals Intact*
- Pass2 pts
- Partial1 pt
- Fail0 pts
- N/Aexcluded from denominator
Glazing Undamaged
- Pass2 pts
- Partial1 pt
- Fail0 pts
- N/Aexcluded from denominator
Hinges And Ironmongery Sound*
- Pass2 pts
- Partial1 pt
- Fail0 pts
- N/Aexcluded from denominator
Signage Correct*
- Yes3 pts
- Partly1 pt
- No0 pts
No Unauthorised Penetrations*
- Pass2 pts
- Partial1 pt
- Fail0 pts
- N/Aexcluded from denominator
Result*
- Pass3 pts
- Pass with conditions2 pts
- Fail0 pts
Photo
Work Order ID
Links to MNT-002 Work Order ID
Propping investigation
2 fieldsAny Door Found Propped*
- No3 pts
- Yes0 pts
Why It Was Propped
Usually a workflow problem. Repeated propping means the door is in the wrong place or needs a hold open device.
Related records
1 fieldFire Risk Assessment ID
The assessment that set the compartmentation.
Links to SAF-115 Assessment ID
Result
11 fieldsItems Assessed*
Excludes anything marked N/A.
Items Failed*
Score Percent*
Calculated on submission. High is good. N/A items leave the denominator.
Result Band*
- Pass3 pts
- Caution1 pt
- Fail0 pts
Completeness Percent*
How much of the template was actually answered. A high score on a half completed form is not a high score.
Action Required*
Raise the action record, then enter its reference here.
- No2 pts
- Yes0 pts
Priority
- High0 pts
- Medium1 pt
- Low3 pts
CAPA ID
Format CAPA-2026-00000.
Links to FDN-014 CAPA ID
Action Owner
Completed By*
Signature*
SAF-114 · record IDs look like INSP-2026-000 · Links Site
Open in KnowellaRun it with agents
From a document you fill in to a programme that runs itself
The form is the easy part. What actually fails is a propped-door finding closing without its cause recorded, and the annual qualified-person examination lapsing behind a run of clean quarterly checks.
Holds the fire door inspection library against the site's door register, routes each record to facilities, and flags doors with repeat propping findings.
Turns a failed closer, seal or hold-open device into a work order automatically, so the fix is tracked rather than noted and left.
Schedules the qualified-person annual NFPA 80 examination against the contractor who holds that duty, separate from the quarterly cycle.

Watches for the same door recurring as propped across cycles with no cause recorded, and surfaces the pattern before it becomes an incident.
This template lives in KnowSafe — safety and compliance. Incidents, hazards, permits, inspections and the critical controls behind them.
Meet KnowSafe→Glossary
Fire Door Inspection definitions and key terms
- Self-closing device
- The mechanism that returns a fire door to the closed and latched position from any open angle without manual assistance, tested as part of the assembly's rating.
- Intumescent seal
- A strip fitted around a door or frame that expands under heat to fill the gap and maintain the fire rating during a fire.
- Smoke seal
- A brush or fin seal fitted to a door assembly to restrict cold smoke passage before heat activates the intumescent seal.
- Fire rating
- The time a door assembly is tested to resist fire spread, commonly 30, 60, 90 or 120 minutes, which sets the maintenance tolerance for gaps, seals and hardware.
- Compartmentation
- The strategy of dividing a building into fire-resisting sections so a fire is contained, with fire doors as one of the elements that maintain each compartment's boundary.
FAQ
Frequently asked questions about fire door inspection
How often should fire doors be inspected?+
This template runs quarterly, which is more frequent than the NFPA 80 minimum of an annual examination by a qualified person. The quarterly cycle is a functional and condition check; it supplements the annual examination rather than replacing it.
Who can carry out this check versus the NFPA 80 annual examination?+
Facilities can carry out the quarterly functional check described here. The annual examination under NFPA 80 must be performed by a person qualified to assess the assembly against its listing, and the two records should be tracked separately.
Why does a propped door matter if it was closed again straight away?+
Because closing it addresses that one moment, not the reason it was propped. A door propped for traffic, ventilation or moving materials will be propped again unless the cause is fixed, and every minute it stands open is a minute the compartment it protects is not protected.
What if the door still closes and latches but has a hole drilled through it?+
It fails. An unauthorised penetration voids the fire rating regardless of how well the door closes, because the rating covers the whole assembly as tested, not just its closing action.
Does a good quarterly result mean the annual qualified-person inspection is current?+
No. Track the annual NFPA 80 examination date independently. A door can pass every quarterly functional check and still be overdue for the technical examination that verifies the assembly in full.
What should happen when the same door keeps getting propped?+
Stop treating each occurrence as an isolated finding and investigate the cause: traffic route, a poor closer, ventilation, or materials movement. Repeated propping usually means the door is in the wrong place for the workflow or needs a listed hold-open device, not another reminder to keep it shut.
Keep going
Related templates and programmes
Industries this is written for
Programmes this belongs to
Used together in Emergency Preparedness
Contractor Emergency Drill Participation
Records contractor involvement in an evacuation or emergency drill, including whether they were accounted for
Site Resilience and Continuity Plan
Sets out how the site keeps operating or recovers after loss of power, refrigeration, water, IT, key equipment or people
Business Continuity Exercise Record
Records a test of the continuity plan, what worked and what did not
Environmental Spill Drill Record
Records a practice spill response, timed from discovery to containment
Emergency Response Plan
Sets out what happens in a fire, medical emergency, spill, power failure or evacuation, including who does what
Evacuation Drill Record
Records a practice evacuation, including clearance time, headcount and anything that went wrong
More in Fire Safety
Fire Extinguisher Inspection
Checks each extinguisher is present, charged, unobstructed and within service date
Fire Alarm System Check
Records testing of detection, sounders and panel function
Sprinkler System Inspection
Checks sprinkler heads, valves, gauges and clearance below heads
Hot Work Fire Watch Log
Records the fire watch kept during and after hot work, including the time the watch ended
Fire Risk Assessment
Assesses fire risk across a building, covering ignition sources, fuel, people, detection and escape
Fire Pump Test Record
Records the routine run test of a fire pump, including pressure, flow and run time

Written and reviewed by
Siddarth Singh
Founder & Chief Executive Officer, Knowella
Certified Safety Professional and industrial and systems engineer with more than a decade inside food supply chain, freight and manufacturing operations. This page was written against the current text of the standards it cites, not against secondary summaries of them.
- Certified Safety Professional (CSP), Board of Certified Safety Professionals
- MBA, University of Chicago Booth School of Business
- MS and BS, The Ohio State University, Industrial and Systems Engineering
- Six Sigma Black Belt
Sources and last review. Reviewed 16 August 2026 against:
- NFPA 80 — Standard for Fire Doors and Other Opening Protectives
- Regulatory Reform (Fire Safety) Order 2005 (UK)
- BS 8214 — Code of practice for fire door assemblies (UK)
- EN 1634-1 — Fire resistance and smoke control test for door and shutter assemblies
This page is general guidance, not legal advice. Confirm requirements with your jurisdiction’s regulator.