Safety Device Test Record

The failure mode is rarely a device that was missed. It is a device tested the easy way. Somebody injects a signal at the logic solver, watches the alarm annunciate, signs the sheet and moves on, while the final element that actually stops the process has not moved in nine years. The record says the trip was proof tested. What was proof tested was a lamp.

KnowMaintainRecordMNT-06246 fields across 3 sectionsFull researchSee the form

Reviewed by Siddarth SinghCSPLast reviewed 16 August 2026

Basis
IEC 61511, ASME BPVC
Workspace
KnowMaintain
Form type
Record
Review trigger
Statutory or SIL derived proof test interval, and after any replacement or set point change
Completed by
A competent technician, countersigned by the engineering manager

The short version

  • The as found set point is the only field here that carries information. If technicians adjust first and record second, the record becomes a certificate rather than a data source and drift trending is impossible.
  • Test Method is scored for a reason. Simulation and partial stroke leave part of the loop unproven, and IEC 61511 credits only the coverage the test achieved.
  • Sealed Or Locked After Test is not tidiness. An unsealed relief valve after a bench test has a set point nobody can defend at the next examination.
  • A failed device must be analysed, not swapped. A device that did not operate is evidence about every identical device on the same duty across the site.

What this is

What is a safety device test record?

What is a safety device test record?

It is the evidence that a protective device was demonstrated to operate at its set point on a stated date, by a stated method. It covers mechanical protection such as relief valves and bursting discs, and instrumented protection such as trips, switches and safety instrumented functions. It converts a device from an assumed control into a proven one.

How does a proof test differ from a functional check?

A proof test reveals dangerous undetected failures, so it must exercise the whole chain from sensor through logic solver to final element. A functional check may confirm only part of that chain. Under IEC 61511 the proof test interval feeds the SIL calculation, so a test covering less than the whole loop invalidates the failure rate the design relied on.

What do as found and as left set points mean?

As found is the value the device actually operated at when first tested, before anything was touched. As left is the value after adjustment. Only the as found figure carries diagnostic value, because it shows how far the device drifted in service and whether the interval is short enough.

Scope

When is a safety device test record required?

This record proves a protective device operates at its set point. It is not a general maintenance record, not a control instrument accuracy check, and not the place to argue about the interval. Mixing those in makes it impossible to report proof test coverage separately from routine calibration.

Use this template when

  • A relief valve, bursting disc, trip, switch or interlock is due its statutory or risk based proof test
  • A protective device has been replaced, repaired or reset and needs re-proving before the plant runs
  • A device operated in service unexpectedly and its behaviour and condition need recording
  • A safety instrumented function is being tested end to end in a SIL verification cycle
  • An audit has questioned whether a listed device has ever actually been tested

Do not use it for

  • Maintenance Calibration Record, which covers accuracy of workshop instruments, not the operation of a protective device
  • Instrument Loop Check, which verifies a control instrument reads correctly and carries no set point or trip evidence
  • Calibration Schedule Review, where the argument about interval length belongs, using the drift history this record produces
  • Out of Tolerance Impact Review, which assesses what was affected once a device is found to have been wrong
  • Test Equipment Register, which holds the calibration status of the calibrators used here, not the result itself

Compliance mapping

Which IEC 61511 requirements does this satisfy?

The template sits between functional safety and pressure equipment law. IEC 61511 governs instrumented protection, ASME BPVC and the national pressure regimes govern mechanical relief devices, and process safety law requires deficiencies to be corrected before further use.

ClauseRequirementWhere it lands
IEC 61511-1, cl.5People carrying out proof testing must be competent for that activity, with competence documented.Outcome
IEC 61511-1, cl.10The safety requirements specification must state the hazardous event each function prevents, with its set point and required response.Header
IEC 61511-1, cl.11The system must act within the process safety time, so response observed on test is judged against that figure rather than against comfort.Test
IEC 61511-1, cl.16Proof testing at the interval assumed in SIL verification, revealing dangerous undetected failures across the whole function.Test
IEC 61511-1, cl.19Test evidence forms part of the safety lifecycle record and must be retrievable for the life of the function.Outcome
ASME BPVC Section VIII Div. 1, UG-125Vessels must be protected by relief devices set so pressure cannot exceed the permitted margin above MAWP.Header
ASME BPVC Section VIII Div. 1, UG-136Relief valves must carry an intact seal on the adjustment after setting, so the set point cannot be altered undetected.Test
29 CFR 1910.119(j)Mechanical integrity requires testing of relief and vent systems, and correction of deficiencies before further use.Outcome

What it does not cover

  • Simulation on a function whose SIL claim assumed full coverage, which means the failure rate credited in design has never been tested for.
  • An as found set point identical to nameplate on every record, which means values are transcribed rather than measured and the interval cannot be defended.
  • Test Equipment Calibrated answered Overdue with a pass still recorded, which means the measurement certifying the device was itself unverified.
  • Sealed Or Locked After Test answered No with no follow up, which means the set point can be altered by anyone with a spanner.
  • Equipment Safe To Operate answered Yes where Test Result is Fail, which means the record contradicts itself and reads as a shutdown avoided.

Global

Safety Device Test Record requirements by country

Proof testing is regulated under process safety law rather than general maintenance law. The three regimes below cover most sites using this template, and differ mainly in who sets the interval.

United States

OSHA Process Safety Management, 29 CFR 1910.119(j)

Mechanical integrity for covered processes, with testing following recognised and generally accepted good engineering practice.

The operator sets frequency but must justify it against manufacturer guidance and operating experience, which is what the as found history provides. Deficiencies must be corrected before further use, so an Equipment Safe To Operate answer of No carries legal weight.

United Kingdom

Pressure Systems Safety Regulations 2000, reg.8 and reg.9

Relief devices on a relevant pressure system must sit in a written scheme of examination drawn up by a competent person, and be examined in accordance with it.

The interval is not the operator's to choose. Test Interval Months and Statutory Requirement must reflect the written scheme, and a Within Interval answer of Overdue is a breach rather than a housekeeping slip.

European Union

Seveso III Directive 2012/18/EU, Annex III

Establishments must operate a safety management system covering operational control and maintenance of safety critical equipment.

Competent authority inspections routinely sample proof test records. One naming the hazardous event in Protects Against and linking a Critical Control ID is far easier to defend than a bare pass sheet.

How to complete it

How to complete a safety device test record, step by step

Filling the fields is trivial. Four judgements decide whether the finished record survives an examination or an incident investigation.

Whether the method actually proves the function

Test Method is a decision, not a description of what was convenient. Partial stroke proves a valve is not seized but not that it closes fully. Bench test proves a relief valve lifts but not that installed pipework behaves the same way. Simulation proves the logic only. If the method does not cover the chain named in Protects Against, schedule the missing coverage rather than letting Test Result imply more than was shown.

Whether the as found value is genuinely as found

Lift, read, record, then adjust. Where As Found Set Point differs from the nameplate value in Set Point, answer Within Tolerance As Found against the device specification, not against whether it felt close enough. The Marginal option exists so near misses stay visible in trending instead of being rounded up to Yes.

Whether the plant can run before the action closes

Equipment Safe To Operate carries the operational consequence. With restrictions is legitimate, but it obliges someone to state and communicate the restriction, and must not be used to dodge a shutdown the Test Result already implies. Where the answer is No, the record has to reach the engineering manager on shift, not at week end.

Whether a failure is treated as a population signal

Failed Device Analysis is not a repair note. A relief valve that failed because the seat corroded is telling you about every identical valve on the same duty. The judgement is whether the finding is device specific or systemic, and if systemic the CAPA covers the population, not the tag.

What auditors find

Most common safety device test record findings

These recur when proof test records are sampled, with the clause each lands against.

FindingClauseWhat fixes it
Trip tested by injecting a signal at the logic solver, final element never stroked.IEC 61511-1, cl.16Restrict Test Method to Full functional test where the SIL claim depends on complete coverage.
As Found and As Left set points identical on every record for a device with known drift.IEC 61511-1, cl.16Enforce recording the first lift value before adjustment, and review the as found series at the Calibration Schedule Review.
Relief valve returned to service after bench test with no seal fitted or condition recorded.ASME BPVC Section VIII Div. 1, UG-136Make Sealed Or Locked After Test a stop condition, with Not applicable reserved for devices with no adjustable element.
Test performed with a pressure calibrator whose own calibration had lapsed.29 CFR 1910.119(j)Answer Test Equipment Calibrated from the Test Equipment Register, and treat Overdue as invalidating the result until repeated.
Protects Against left as a generic phrase such as overpressure, with no named event.IEC 61511-1, cl.10Require the specific scenario and link the Critical Control ID so the set point traces back to the hazard study.
Devices carried as Overdue for several cycles with no restriction placed on the plant.Pressure Systems Safety Regulations 2000, reg.9Drive an exception from Within Interval into the action route and reassess Equipment Safe To Operate at each deferral.

Case in point

Case in point: the interlock proven on paper for nine years

A chilled water plant carried a high level trip on a buffer vessel, listed as a safety instrumented function with a claimed SIL 1. Proof test records went back nine years without a single fail, all using the same method: the transmitter was ranged down at the head until the trip annunciated, the alarm was acknowledged, the sheet was signed. Nobody had ever closed the inlet valve as part of the test.

The valve was found seized during an unrelated outage, sitting around eighteen per cent open and unable to drive closed against line pressure. Nine years of passes had proven the sensor and the logic solver and nothing else. The corrective action was not a new valve. It was a rule that Test Method could not be anything but Full functional test for that function, and a review of every other function whose history showed the same shortcut.

The template

The template, field by field

The form exactly as it installs. Every field, option, score and conditional rule is editable, and the links to other templates come with it.

46fields
3 sections
Reference
MNT-062
Archetype
Record
Record ID
SDT-2026-000
Scoring
Pass or fail
Direction
High is good
Singleton
No
Basis
IEC 61511, ASME BPVC
Links
Links Asset, Critical Control
Tags
Calibration, Safety
Sections
3
Fields
46
Follow up fields
5
Repeating sections
0
Links out
4
Field typesOwn ID, generated on saveCase thread and parentPick list from a registryLinked to another templateFollow up, dashed outlineScored

Header

19 fields
Text

Test ID*

Generated on save

Auto sequence. Format SDT-2026-000.

The record's own ID. Other templates point at this value.

Single Choice

Status*

Scored

Drives who this goes to next.

  • Planned2 pts
  • In progress2 pts
  • Complete3 pts
  • Deferred0 pts
  • Open0 pts
  • Closed3 pts
  • Overdue0 pts
Date & Time

Date and Time*

Users

Raised By*

Pick List

Site*

From FDN-001 Site NameFilter: Status is Active
Text

Site ID*

Linked

Format SITE-000.

Links to FDN-001 Site ID

Single Choice

Area

Optional

The area within the site.

Cutting roomBoning hallPackingChill storeFreezerPasteurisingFillingCulture roomDespatchYardWorkshopPlant roomOffices
Location

Exact Location

Optional

Drop a pin for anything hard to find.

Pick List

Asset*

From FDN-002 Asset NameFilter: Site matches, Status is Active
Text

Asset ID*

Linked

Format AST-0000.

Links to FDN-002 Asset ID

Info

Untested Is Unproven

A relief valve that has never lifted, a trip that has never operated and an interlock that has never been tested are assumptions, not protective controls.

Single Choice

Device Type*

Relief valve, bursting disc, high level trip, temperature trip, pressure switch, interlock or safety instrumented function.

Relief valveBursting discHigh level tripTemperature tripPressure switchInterlockSafety instrumented function
Text

Device Reference*

Text

Set Point*

Numeric Answer

Test Interval Months*

Single Choice

Within Interval*

Scored
  • Yes3 pts
  • Overdue0 pts
Single Choice

Statutory Requirement*

YesNo
Text

Protects Against*

The specific event this device prevents. If nobody can state it, the set point is probably wrong.

Text

Critical Control ID

OptionalLinked

Links to FDN-011 Control ID

Test

12 fields
Single Choice

Test Method*

Scored

Full functional test, partial stroke, bench test or simulation. Full functional is the only one that proves the whole chain.

  • Full functional testnot scored
  • Partial strokenot scored
  • Bench testnot scored
  • Simulationnot scored
Text

Test Equipment Used

Optional
Single Choice

Test Equipment Calibrated*

Scored
  • Yes3 pts
  • Overdue0 pts
Text

As Found Set Point*

Text

Operated At*

Single Choice

Within Tolerance As Found*

Scored
  • Yes3 pts
  • Marginal1 pt
  • No0 pts
Single Choice

Operated Fully*

Scored
  • Yes3 pts
  • Partly1 pt
  • No0 pts
Single Choice

Reset Correctly*

Scored
  • Yes3 pts
  • No0 pts
Single Choice

Response Time Acceptable

OptionalScored
  • Yes3 pts
  • Marginal1 pt
  • No0 pts
Single Choice

Adjustment Made*

YesNot neededNo
Text

As Left Set Point

Optional
Single Choice

Sealed Or Locked After Test*

Scored
  • Yes3 pts
  • Not applicable3 pts
  • No0 pts

Outcome

15 fields
Single Choice

Test Result*

Scored
  • Pass3 pts
  • Pass with note2 pts
  • Fail0 pts
Single Choice

Device Replaced

Optional
YesNo
File Upload

Certificate Attached

Optional
Text

Failed Device Analysis

OptionalShows if Test Result equals Fail

A device that failed to operate needs investigation, not just replacement.

Text

Case ID

OptionalThread keyShows if Test Result equals Fail

Thread key

Single Choice

Equipment Safe To Operate*

Scored
  • Yes3 pts
  • With restrictions1 pt
  • No0 pts
Date & Time

Next Test Due*

Single Choice

Action Required*

Scored

Raise the action record, then enter its reference here.

  • No2 pts
  • Yes0 pts
Single Choice

Priority

OptionalScoredShows if Action Required equals Yes
  • High0 pts
  • Medium1 pt
  • Low3 pts
Text

CAPA ID

OptionalLinkedShows if Action Required equals Yes

Format CAPA-2026-00000.

Links to FDN-014 CAPA ID

Users

Action Owner

OptionalShows if Action Required equals Yes
Users

Technician*

Signature

Signature*

Users

Engineering Manager*

Signature

Second Signature*

MNT-062 · record IDs look like SDT-2026-000 · Links Asset, Critical Control

Open in Knowella

Run it with agents

From a document you fill in to a programme that runs itself

Proof testing fails on coordination, not technique. The interval slips, the calibrator lapses, the failed device is replaced without anyone asking why.

KnowMaintain

Holds the device population against the asset register, drives the interval from the written scheme, and raises the exception when Within Interval turns Overdue.

KnowSafe

Owns the link between the device and the hazardous event named in Protects Against, so a failed test shows as a degraded layer of protection rather than a maintenance job.

KnowQuality

Keeps the test equipment register current so Test Equipment Calibrated is answered from live data, and carries the out of tolerance impact review.

Ella
Ella

Pulls the as found series across the device population, flags functions whose recorded method has never been a full functional test, and holds every write for approval before it touches a record.

This template lives in KnowMaintain — asset maintenance. Work orders, planned maintenance, calibration, reliability and shutdowns.

Meet KnowMaintain→

Glossary

Safety Device Test Record definitions and key terms

Proof test
A periodic test to detect dangerous failures not revealed by diagnostics, restoring the function to an as new condition as far as practicable. Its interval feeds the SIL calculation.
As found
The value or condition of a device at the moment of test, before any adjustment. The only source of drift information on the record.
Partial stroke test
Moving a valve through limited travel to confirm it is not seized without interrupting the process. It improves diagnostic coverage but does not replace a full proof test.
Set point
The process value at which a protective device is intended to operate. For relief devices it is normally stamped on the nameplate and sealed after setting.
Process safety time
The interval between the onset of a deviation and the hazardous event. A protective function must complete its action within that time to be credited as a layer of protection.

FAQ

Frequently asked questions about safety device test record

How is the test interval decided?+

For statutory devices it comes from the written scheme of examination and is not the operator's to change. For instrumented functions it comes from the SIL verification, where a longer interval means a higher probability of failure on demand. Test Interval Months should trace to one of those two.

Can a bench test replace an in situ test for a relief valve?+

It proves the valve lifts at set pressure, the main statutory requirement, but not that the installed inlet and discharge pipework behave as designed. Where inlet pressure loss or back pressure is a known concern, the bench result needs an installation review alongside it.

Why does the template require two signatures?+

The technician and the engineering manager answer different questions. The technician attests to what was observed. The manager accepts the consequence recorded in Equipment Safe To Operate and Next Test Due. Separating them stops a shutdown decision being taken quietly at the point of test.

What should happen when a device fails?+

A Fail opens Failed Device Analysis and Case ID. The device is repaired or replaced, retested and recorded again, and the analysis asks whether identical devices on similar duty share the mechanism. Replacement alone closes the tag and leaves the population risk untouched.

Does Marginal count as a pass?+

It scores one rather than zero, so it does not fail the record, but it stays visible. A run of Marginal answers on one device is a stronger case for shortening the interval than a single outright failure.

Can the template be changed?+

Yes. Fields, options, scores and conditional rules are editable, and the links to the asset and critical control registers come with it. The edit worth making early is tightening Test Method for named safety instrumented functions.

Keep going

Related templates and programmes

Siddarth Singh

Written and reviewed by

Siddarth Singh

Founder & Chief Executive Officer, Knowella

Certified Safety Professional and industrial and systems engineer with more than a decade inside food supply chain, freight and manufacturing operations. This page was written against the current text of the standards it cites, not against secondary summaries of them.

  • Certified Safety Professional (CSP), Board of Certified Safety Professionals
  • MBA, University of Chicago Booth School of Business
  • MS and BS, The Ohio State University, Industrial and Systems Engineering
  • Six Sigma Black Belt
Verify with BCSP →

Sources and last review. Reviewed 16 August 2026 against:

  • IEC 61511-1:2016, Functional safety for the process industry sector, cl.10, cl.11, cl.16 and cl.19
  • ASME BPVC Section VIII Division 1, UG-125 to UG-136, pressure relief devices
  • OSHA 29 CFR 1910.119(j), Process safety management: mechanical integrity
  • Pressure Systems Safety Regulations 2000 (SI 2000/128), reg.8 and reg.9
  • Seveso III Directive 2012/18/EU, Annex III, safety management system requirements

This page is general guidance, not legal advice. Confirm requirements with your jurisdiction’s regulator.