A fixed installation inspection is the periodic, whole-installation check of wiring, circuits, earthing and protective devices, carried out by a competent contractor and reported against a classification scheme. Its recurring failure is what happens either side of it: the sample is small enough to miss the fault, prior findings were never closed, and a satisfactory certificate is issued over both.

KnowSafeInspectionSAF-16040 fields across 4 sectionsFull researchSee the form

Reviewed by Siddarth SinghCSPLast reviewed 16 August 2026

Basis
ISO 45001 cl.8.1
Workspace
KnowSafe
Form type
Inspection
Periodicity
Set by installation type and condition, not a fixed default
Carried out by
A competent, registered contractor, on a sample of the installation

The short version

  • The report is only as good as the sample. A ten per cent sample on a large installation says little about the other ninety per cent, and the record should state the percentage rather than imply full coverage.
  • Danger present findings are not paperwork for later. They require action before the inspector leaves, or a documented interim measure, because the classification exists to force that response.
  • A satisfactory assessment issued while previous observations remain unrectified is not defensible. The cycle only closes when last time's findings were addressed, not when this inspection was completed.
  • The statutory interval is a maximum, not a target. Condition, environment and age should shorten it, and the record should show that judgement was made rather than a default carried forward unexamined.

What this is

What is a fixed installation inspection?

What is a fixed installation inspection?

A periodic examination and test of the electrical installation serving a site or building: distribution boards, fixed wiring, earthing and bonding, and protective devices. It is testing against a defined standard, not troubleshooting a fault or checking a single piece of equipment.

What do the classification codes mean?

Danger present means a risk of injury exists now and requires immediate remedial action. Potentially dangerous means the observation could become dangerous and needs urgent investigation. Improvement recommended flags a departure worth addressing without indicating non-compliance. Further investigation required means the inspector could not determine whether a danger exists within the inspection's scope.

Who is competent to carry out the inspection?

Someone holding a recognised electrical qualification and current registration with an accredited scheme, working to the current wiring standard. Competence is assessed against the specific installation type; competence for a general commercial installation does not carry over to a hazardous-area or high-voltage one.

Scope

When is a fixed installation inspection required?

This is the periodic, whole-installation inspection. It sits above equipment- and panel-level checks and should not be used as a substitute for either, or treated as satisfied by them.

Use this template when

  • The statutory or programme-defined interval for the fixed installation has been reached
  • A change to the installation, supply or building use requires a fresh periodic inspection
  • An insurer, landlord covenant or duty holder requires a current condition report
  • The previous report's findings are due for verification as part of this cycle
  • A post-incident inspection is required after an electrical fault, fire or near miss

Do not use it for

  • Electrical Panel Inspection (SAF-161), the more frequent, narrower visual and thermal check of a specific distribution board, not the statutory whole-installation report
  • Electrical Safety Risk Assessment (SAF-156), which assesses shock and arc flash risk from work on the installation rather than its physical condition
  • Arc Flash Study Record (SAF-157), which records the incident energy calculation and PPE category at a panel, fed by this inspection rather than replacing it
  • Live Working Justification Record (SAF-158), which records why work was carried out live, not the condition of the installation worked on
  • New installation or major alteration work, which needs an electrical installation certificate rather than a condition report

Compliance mapping

Which ISO 45001 cl.8.1 requirements does this satisfy?

The duty to maintain the fixed installation is set in general terms by workplace electrical safety law; the method and classification scheme come from the wiring standard the inspection is written against.

ClauseRequirementWhere it lands
Electricity at Work Regulations 1989, reg.4(2)Systems maintained so as to prevent danger, so far as reasonably practicableHeader
BS 7671 (IET Wiring Regulations), classification codesObservations classified C1 danger present, C2 potentially dangerous, C3 improvement recommended, or FI further investigationObservations
ISO 45001 cl.8.1Operational controls established and applied to eliminate hazards and reduce riskResult
ISO 45001 cl.9.1.1Monitoring of control effectiveness, including whether prior findings were resolvedScope and method
ISO 45001 cl.10.2Nonconformities addressed with corrective action, ownership and a target dateResult
OSHA 29 CFR 1910.303Electrical equipment and wiring maintained free of recognised hazardsHeader
Electricity at Work Regulations 1989, reg.4(1)Systems constructed and maintained to prevent danger so far as reasonably practicableHeader

What it does not cover

  • Electrical Panel Inspection, which covers the enclosure, thermal and labelling condition of one distribution board on a quarterly cycle and does not substitute for whole-installation testing.
  • Electrical Safety Risk Assessment, which addresses the risk to a person working on or near the installation, not its physical condition.
  • Arc Flash Study Record, which requires its own incident energy calculation and cannot be inferred from a condition report's pass or fail.
  • New installation certification, which is a distinct certificate confirming design, construction and initial verification, not a periodic condition report.
  • Portable Appliance Test Record, which covers plug-in and portable equipment, not fixed wiring and distribution.

Global

Fixed Installation Inspection requirements by country

Statutory periodic inspection of the fixed installation is a distinctly British instrument; other regimes rely on general maintenance duties or a management-system requirement instead.

United Kingdom

Electricity at Work Regulations 1989, with BS 7671 as the applied standard

Duty holders must maintain the installation to prevent danger; periodic inspection to BS 7671, with classification codes, evidences that.

Insurers, landlords and enforcers treat a current, satisfactory report as primary evidence of compliance; an expired one is a live liability.

United States

OSHA 29 CFR 1910.303 and NFPA 70B maintenance guidance

No federally mandated periodic condition report exists; the duty is to maintain wiring free of recognised hazards, with NFPA 70B offered as guidance.

Absence of a mandated cycle does not remove the duty; an installation left uninspected for years is still exposed under the general maintenance requirement.

International

ISO 45001

The installation is an operational control subject to the requirement to eliminate hazards, reduce risk and monitor control effectiveness.

Certification auditors expect a defined inspection interval, evidence it was met, and evidence prior findings were actually closed.

How to complete it

How to complete a fixed installation inspection, step by step

The template prompts for a classification and a signature. Whether the record is defensible depends on judgements the template does not force.

Treat the sample as a sample, not a survey

State the percentage inspected, sized to the installation's age, history and complexity, not a habitual default. A poor previous report warrants a higher sample than a recently rewired installation, and the record should show that reasoning.

Verify the previous cycle actually closed

A report classifying this cycle's observations without confirming last time's were rectified has only checked half the record. Unaddressed C2 findings carried across multiple cycles mean the installation is not being maintained, whatever this result says.

Danger present is an action, not a classification

A C1 finding means a risk of injury exists now. Recording it and moving on is not compliance with the classification's own definition; the immediate action, or a documented interim safe state, has to exist before the inspector leaves site.

Set the next interval by condition, not by habit

The statutory interval is a maximum permitted gap, not a recommended one. An installation in a harsh environment, showing deterioration, or carrying unresolved items in volume should be reviewed sooner, with the record showing why.

What auditors find

Most common fixed installation inspection findings

Findings cluster around what the sample actually covered and whether the classification scheme was applied with any rigour.

FindingClauseWhat fixes it
Sample percentage too low to represent a large or ageing installation.BS 7671, periodic inspection guidanceSize the sample to age, history and complexity, and state the percentage and justification in the report.
Report issued as satisfactory while previous cycle's observations remain unrectified.ISO 45001 cl.9.1.1Verify closure of prior findings before recording the overall assessment; do not rate the cycle satisfactory over unresolved items.
Danger present findings recorded without evidence of immediate action or an interim safe state.Electricity at Work Regulations 1989, reg.4(2)Record the immediate action taken; where none was possible, document the interim isolation applied.
Classification code applied inconsistently, with C2-grade observations recorded as C3 to avoid remedial cost.BS 7671, classification codesCalibrate inspectors against the standard's definitions, and audit a sample of classifications against the underlying observation.
Next inspection interval carried forward unchanged despite deteriorating condition or a poor result.ISO 45001 cl.8.1Set the next interval from this inspection's findings, shortening it where condition or unresolved items warrant.
Contractor's competence and scheme registration not verified or evidenced on the record.Electricity at Work Regulations 1989, reg.4(2)Record registration status at booking, not retrospectively, and decline the report where it cannot be evidenced.

Case in point

Case in point: the satisfactory report with an unexamined ninety per cent

A manufacturing site's fixed installation was inspected on its five-year statutory cycle. The contractor sampled ten per cent of the boards, found two improvement-recommended items on ageing circuits, and issued a satisfactory assessment with a note to address the improvements at convenience.

Fourteen months later, a board outside the sample developed a loose connection and overheated, triggering a small fire caught by the smoke system before it spread. That board sat untouched across three consecutive cycles. The satisfactory report had, in practical terms, examined a tenth of the installation and said nothing about the rest.

The template

The template, field by field

The form exactly as it installs. Every field, option, score and conditional rule is editable, and the links to other templates come with it.

40fields
4 sections
Reference
SAF-160
Archetype
Inspection
Record ID
INSP-2026-000
Scoring
Observations open
Direction
Low is good
Singleton
Yes
Basis
ISO 45001 cl.8.1
Links
Links Work orders, Contractor records
Tags
Electrical, Installation
Sections
4
Fields
40
Follow up fields
4
Repeating sections
1
Links out
4
Field typesOwn ID, generated on saveCase thread and parentPick list from a registryLinked to another templateFollow up, dashed outlineScored

Header

14 fields
Text

Inspection ID*

Generated on save

Auto sequence. Format INSP-2026-00000.

The record's own ID. Other templates point at this value.

Single Choice

Status*

Scored

Drives who this goes to next.

  • Planned2 pts
  • In progress2 pts
  • Complete3 pts
  • Deferred0 pts
  • Open0 pts
  • Closed3 pts
  • Overdue0 pts
Date & Time

Date and Time*

Users

Completed By*

Pick List

Site*

From FDN-001 Site NameFilter: Status is Active
Text

Site ID*

Linked

Format SITE-000.

Links to FDN-001 Site ID

Single Choice

Area

Optional

The area within the site.

Cutting roomBoning hallPackingChill storeFreezerPasteurisingFillingCulture roomDespatchYardWorkshopPlant roomOffices
Location

Exact Location

Optional

Drop a pin for anything hard to find.

Text

Installation Or Distribution Board*

Single Choice

Inspection Type*

ScheduledUnscheduledFollow upPost incident
Single Choice

Statutory Interval*

AnnualThree yearsFive years
Pick List

Contractor

OptionalFrom FDN-005 Vendor Name
Single Choice

Inspector Competent And Registered*

Scored
  • Yes3 pts
  • No0 pts
Single Choice

Within Interval*

Scored
  • Yes3 pts
  • Overdue0 pts

Scope and method

3 fields
Numeric Answer

Percentage Sampled*

Scored

Sampling is normal, but a small sample on a large installation says very little.

Single Choice

Previous Report Reviewed*

Scored
  • Yes3 pts
  • No0 pts
Single Choice

Previous Observations Rectified*

Scored
  • All3 pts
  • Most1 pt
  • Few0 pts

Observations

Repeats6 fields
Text

Observation*

Text

Location*

Single Choice

Classification Code*

Scored

Danger present and potentially dangerous both require action. Improvement recommended does not, but repeated ones point at a neglected installation.

  • Danger present0 pts
  • Potentially dangerous0 pts
  • Improvement recommended2 pts
  • Further investigation required1 pt
Text

Immediate Action Taken

OptionalShows if Classification Code contains Danger present
Users

Owner*

Date & Time

Target Date*

Result

17 fields
Numeric Answer

Danger Present Observations*

Scored
Numeric Answer

Potentially Dangerous Observations*

Scored
Numeric Answer

Improvement Recommended

Optional
Single Choice

Overall Assessment*

Scored
  • Satisfactory3 pts
  • Unsatisfactory0 pts
Single Choice

Certificate Or Report Issued*

Scored
  • Yes3 pts
  • Pending1 pt
  • No0 pts
File Upload

Report Attached

Optional
Single Choice

Remedial Work Ordered*

Scored
  • Yes3 pts
  • Not needed3 pts
  • No0 pts
Text

Work Order ID

OptionalLinked

Links to MNT-002 Work Order ID

Date & Time

Next Inspection Due*

Single Choice

Action Required*

Scored

Raise the action record, then enter its reference here.

  • No2 pts
  • Yes0 pts
Single Choice

Priority

OptionalScoredShows if Action Required equals Yes
  • High0 pts
  • Medium1 pt
  • Low3 pts
Text

CAPA ID

OptionalLinkedShows if Action Required equals Yes

Format CAPA-2026-00000.

Links to FDN-014 CAPA ID

Users

Action Owner

OptionalShows if Action Required equals Yes
Users

Inspector*

Signature

Signature*

Users

Engineering Manager*

Signature

Second Signature*

SAF-160 · record IDs look like INSP-2026-000 · Links Work orders, Contractor records

Open in Knowella

Run it with agents

From a document you fill in to a programme that runs itself

The report exists. What fails is the interval that slips, the sample never sized to the installation, and the prior finding that quietly carries forward unclosed.

KnowSafe

Tracks the inspection interval against installation type and condition, flags an approaching statutory maximum, and checks prior observations were closed before the next cycle is filed.

KnowMaintain

Links danger present and potentially dangerous findings to work orders, and confirms remedial work was completed rather than only raised.

KnowContractor

Holds contractor competence and scheme registration on file, checked against the record at the point the inspection is booked.

Ella
Ella

Watches for reports issued satisfactory while prior findings remain open, and raises the inconsistency before the record is accepted.

This template lives in KnowSafe — safety and compliance. Incidents, hazards, permits, inspections and the critical controls behind them.

Meet KnowSafe→

Glossary

Fixed Installation Inspection definitions and key terms

EICR
Electrical Installation Condition Report: the formal report from a periodic inspection, recording observations against the wiring standard's classification scheme.
Classification code
The C1, C2, C3 or FI rating applied to an observation: danger present, potentially dangerous, improvement recommended, or further investigation required.
Duty holder
The person or organisation with legal responsibility for the safety of the fixed installation, typically the employer, landlord or owner.
Periodicity
The maximum interval between periodic inspections, set by installation type, environment and use, shortened where condition warrants.
Sample
The proportion of the installation actually inspected and tested, which should be stated and justified rather than implied as complete coverage.

FAQ

Frequently asked questions about fixed installation inspection

How large should the inspection sample be?+

Large enough to reflect the installation's age, history and complexity, not a fixed percentage applied everywhere. A clean recent history can be sampled lightly; a poor previous report or known deterioration should be sampled more heavily, with the report stating why.

What happens when a danger present item is found?+

It requires action before the inspector leaves site, or a documented interim measure such as isolation. A danger present finding recorded and left for the next work order is not consistent with what the classification means.

Can the statutory interval be extended?+

The interval is a maximum permitted gap, not a fixed schedule to be used in full every time. It can be shortened by condition or history, but extending beyond the maximum removes the basis for calling the installation compliant.

Does a satisfactory report mean the whole installation is safe?+

It means the sampled portion, tested at the time, met the standard. It does not extend to the unsampled remainder, and a report that omits its sample size invites exactly that overreading.

Who has to be competent, the individual or the company?+

Both matter, but the inspector's qualification and current scheme registration is what the sign-off depends on. Company accreditation does not substitute for verifying the specific inspector's competence for that installation type.

What is the difference between this and an electrical panel inspection?+

This is the periodic, whole-installation report at the statutory interval, carried out by a competent contractor. A panel inspection is a narrower, more frequent visual and thermal check of a single distribution board, usually run by maintenance.

Keep going

Related templates and programmes

Siddarth Singh

Written and reviewed by

Siddarth Singh

Founder & Chief Executive Officer, Knowella

Certified Safety Professional and industrial and systems engineer with more than a decade inside food supply chain, freight and manufacturing operations. This page was written against the current text of the standards it cites, not against secondary summaries of them.

  • Certified Safety Professional (CSP), Board of Certified Safety Professionals
  • MBA, University of Chicago Booth School of Business
  • MS and BS, The Ohio State University, Industrial and Systems Engineering
  • Six Sigma Black Belt
Verify with BCSP →

Sources and last review. Reviewed 16 August 2026 against:

  • Electricity at Work Regulations 1989, regulation 4 (UK)
  • BS 7671 (IET Wiring Regulations), periodic inspection and classification codes
  • OSHA 29 CFR 1910.303, electrical equipment and wiring
  • ISO 45001:2018 clauses 8.1, 9.1.1 and 10.2

This page is general guidance, not legal advice. Confirm requirements with your jurisdiction’s regulator.